1 User's Guide Getting Started This chapter explains: • Packing the card • Installation Checklist • Card defaults • INTERFACE (EK381V4L 14pin &am
10 3. Select the serial connection (such as COM1). Figure7. Select the serial connection 4. Set the serial line to 2400 baud, 8 data bits, No pa
11 5. Set the PropertiesÆSettingsÆASCII Setup. Figure9. Set the Properties 4. Setting operation menu 4.1. Password menu Type <ENTER> continu
12 4.2. Main menu There are six item can be setting or inquire firmware version, user need base on menu number and enter the correct menu -----------
13 ----------------------------------------------------------------------------- Function Segment Logic ---------------------------------------------
14 4.4. Output Segment Function Configure menu When main menu Type 2 and press Enter. The menu displays the Output Segment Function Configure and cur
15 Function description: 1. Utility Failure: UPS input mains voltage or frequency out of range 2. Battery Low: UPS Battery voltage level is low 3. Gen
16 ----------------------------------------------------------------------------- Segment 6 Function -------------------------------------------------
17 ----------------------------------------------------------------------------- Function Segment Active Delay Time ---------------------------------
18 Enter Y or y. below menu will display as below, if enter any other character, the only main menu displays (see Figure 12) and not show “Default All
19 ----------------------------------------------------------------------------- Exit ---------------------------------------------------------------
2 Card Details
20 614-09976-00
3 INTERFACE (EK381V4L 14pin & RJ45) Segment PIN NO Specification/Function remark Dry contact Segment 1 Segment 2 Segment 3 Segment 4 Segment 5 S
4 Note: Segment 7 (PIN14 & PIN1 / USER SW2) is fixed to UPS On function. Segment 8 (PIN7 & PIN1 / USER SW3) is fixed to UPS Off function
5 INTERFACE (UPS side)Item Specification/Function Pin Assignment - Pin 1 - Pin 2 - Pin 3 - Pin 4 - Pin 5 - Pin 6 - Pin 7 - Pin 8 - Pin 9 - Pin 10
6 Input signals (Segment 6): User can choose one function for a Segment from below table. *Input signal (Segment 6): Description Meaning “1” “0” Batte
7 2. Definitions 2.1. Common items (1) Computer (Software) has Initiative for communicate by this protocol. Computer will send command ended with &l
8 3. Installing 3.1. Installing the Card The Dry contact Management Card can be installed in UPS equipped with a communication bay without turning of
9 3.3. Configuring the Card To configure the card: 1. Verify that the serial cable (supplied) is connected to the card's Settings port and the