17
1)Switch-off picture 2)If it is in single machine mode, the
following will appear
Remember to verify the transfer before proceeding the next step.
3.Remove the locking plate of maintenance switch.
4.Turn OFF the Rectier Input switch and battery fuse.
5.Turn the Maintenance switch to
“
MAINTENANCE
”
side.
6.Turn OFF the Bypass Input switch and N switch.
Comentários a estes Manuais